Power outage DBC (Databarn Capelle) (Status)

« Back

[#958] Power outage DBC (Databarn Capelle) (Status)

Posted: 2021-05-10 05:15

Start: 2021-05-10 12:50:00
End : 2021-05-10 17:00:00

Affects: All services DBC (Databarn Capelle)

We are currently investigating an issue with the power distribution at DBC. The power started to flap at 12:50 and went completely down at 13:00.

We have contacted the datacenter for more information on the issue and are waiting for a response.

Update 13:29:
There is an outage reported by Stedin, we have received notification of an issue in a 100kv substation. More information can be found at https://www.stedin.net/storing-en-onderhoud/overzicht .

Update 17:17:

We received a message from the datacenter:

"We just had a major impact in our power supply due to a problem with Stedin.

The power was cut of at 12:34 and returns after several seconds. The next problem that occurred was a low voltages on 1 feed

https://www.stedin.net/storing-en-onderhoud/storingshistorie

The ups stabilised the drops as it kept on coming and going. For safety measurements we tried to bypass the UPS and put the full load on our generators. But since the power did not fully dropped it declined to bypass. Due to an error the power was cut of for several minutes. "